The Chemical Explosion Suppression System rapidly detect and intervene in the early stages of a combustion reaction injecting a chemical suppressant in to the process within milliseconds. This swift response effectively prevents the escalation of pressure and flames, averting a catastrophic event.
Model | EVES |
Specification | 6L |
Pred, max | <0.1MPa |
Dust type | St1 and St2 non-metallic dust |
Combustion requires dust supplied by air, non-corrosive, non-sticky and non-frictional | |
Installation distance | The shortest installation distance: 4m, fire extinguishing distance: 3m |
Applicable pipe specifications | DN600 and below |
Applicable process | Positive pressure or negative pressure process; working pressure is not higher than one atmosphere (0.1MPa); |
The oxygen content is no higher than the oxygen content in the air (21%); | |
Reusability | The explosion suppression tank needs to be replaced after triggering |
Product performance standards | EN 15089-2014 Explosion isolation systems |
Installation method | Vertical installation |
English
Français
Deutsch
日本語
한국인