Explosion Isolation Pinch Valve

Overview

An active mechanical isolation protection device that collaborates with a control panel and explosion detector. It employs a  rugged  elastomer sleeve and compressed air to rapidly pinch the device into full closure within milliseconds of detection, protecting downstream equipment from flames and pressure.

Features

  • Bi-directionally isolates explosions in the process flow
  • Super fast Interception Valve
  • Designed to prevent explosion propagation
  • Quick reset after activation, avoid downtime
  • No refurbishment needed

Applications & Industries

Technical Parameters

Model EVPV
Specification DN150
Pred, max <0.1465MPa
Dust type St1 and St2 non-metallic dust
Combustion requires dust supplied by air, non-corrosive, non-sticky and non-frictional
Installation distance The shortest installation distance: 8m
The longest installation distance: 20m
Applicable process Positive pressure or negative pressure process; working pressure is not higher than one atmosphere (0.1MPa);
The oxygen content is no higher than the oxygen content in the air (21%);
Reusability Reusable
Product performance standards EN 15089-2014 Explosion isolation systems
Installation method Unrestricted