An active mechanical isolation protection device that collaborates with a control panel and explosion detector. It employs a rugged elastomer sleeve and compressed air to rapidly pinch the device into full closure within milliseconds of detection, protecting downstream equipment from flames and pressure.
Model | EVPV |
Specification | DN150 |
Pred, max | <0.1465MPa |
Dust type | St1 and St2 non-metallic dust |
Combustion requires dust supplied by air, non-corrosive, non-sticky and non-frictional | |
Installation distance | The shortest installation distance: 8m |
The longest installation distance: 20m | |
Applicable process | Positive pressure or negative pressure process; working pressure is not higher than one atmosphere (0.1MPa); |
The oxygen content is no higher than the oxygen content in the air (21%); | |
Reusability | Reusable |
Product performance standards | EN 15089-2014 Explosion isolation systems |
Installation method | Unrestricted |